The heat transfer rate Q̇ follows from one of three formulas, depending on the mechanism: conduction Q̇ = λ · A · ΔT / d, convection Q̇ = α · A · ΔT and radiation Q̇ = ε · σ · A · (T₁⁴ − T₂⁴). The result is a power in watts, and dividing it by the area gives the heat flux q̇ in W/m². The calculator returns both values plus the thermal resistance in K/W.
The heat transfer rate Q̇, also called heat flow rate, is the amount of heat transferred per unit time from a warmer to a colder body. Its unit is the watt (1 W = 1 J/s). Dividing the heat transfer rate by the area it flows through gives the heat flux q̇ = Q̇ / A in W/m².
Reference values at about 20 °C. For thermal interface materials, use the datasheet value. In practice, contact resistances at the interfaces add to the result. λ values in the table →
Each mechanism has its own formula. They share the same structure: the heat transfer rate grows with the area and with the temperature difference. For radiation, however, temperature enters to the fourth power and as an absolute value in kelvin.
Q̇ = λ · A · ΔT / d Conduction (Fourier): heat flow through a flat layer of thickness d, such as a base plate, a ceramic substrate or a thermal paste. Valid for steady-state, one-dimensional conduction.
Q̇ = α · A · ΔT Convection (Newton): heat transfer from a surface to a flowing fluid. ΔT is the difference between wall and fluid temperature, and α combines flow conditions and fluid properties.
Q̇ = ε · σ · A · (T₁⁴ − T₂⁴) Thermal radiation (Stefan-Boltzmann): net exchange between a grey body and large surroundings. Temperatures in kelvin, σ = 5.670 · 10⁻⁸ W/(m²·K⁴).
Q̇ = ṁ · c_p · ΔT Heat flow of a fluid stream: the mass flow rate ṁ and the specific heat capacity c_p give the temperature rise of the coolant between inlet and outlet.
q̇ = Q̇ / A Heat flux: the heat transfer rate per unit of the area it flows through. It shows how concentrated the heat is.
Watch out with radiation: temperatures enter as absolute values in kelvin, T = ϑ + 273.15. Using °C gives wrong results. For conduction and convection, the difference ΔT is all that matters, and it has the same numerical value in K and °C.
Heat transfer rate and temperature difference behave like electric current and voltage. The thermal resistance R_th = ΔT / Q̇ in K/W corresponds to electrical resistance. This lets you calculate entire thermal paths like a circuit.
R_th = ΔT / Q̇ With the total resistance, the heat transfer rate follows directly from Q̇ = ΔT_total / R_total. Conversely, ΔT = Q̇ · R gives the temperature rise across each individual layer.
Calculate thermal resistance: Rth calculator →An IGBT module dissipates 300 W through a base area of 60 cm² (0.006 m²) into a cold plate. In between are 0.1 mm of thermal paste (λ = 3 W/(m·K)) and 10 mm of aluminium EN AW-6060 (λ = 200 W/(m·K)). In the cooling channel, α = 3,000 W/(m²·K) with a wetted area of 120 cm². We are looking for the temperature rise from the module base to the cooling water.
q̇ = 300 W / 0.006 m² = 50,000 W/m² = 5 W/cm² R_TIM = 0.0001 m / (3 W/(m·K) · 0.006 m²) = 0.0056 K/W → ΔT = 1.7 K R_plate = 0.010 m / (200 W/(m·K) · 0.006 m²) = 0.0083 K/W → ΔT = 2.5 K R_conv = 1 / (3,000 W/(m²·K) · 0.012 m²) = 0.0278 K/W → ΔT = 8.3 K R_total = 0.0056 + 0.0083 + 0.0278 = 0.0417 K/W → ΔT_total = 300 W · 0.0417 K/W = 12.5 K The module base sits around 12.5 K above the cooling water temperature, and the convective transfer into the water accounts for the largest share. The TIM layer stands out: 0.1 mm of thermal paste costs 1.7 K, two thirds of what 10 mm of aluminium causes. At 5 W/cm², the application is clearly in liquid cooling territory.
Simplification: one-dimensional thermal path without heat spreading and without contact resistances. In practice, the base plate spreads the heat over a larger area, while contact resistances add up at every interface. With R_th,JC from the datasheet, you can then calculate the junction temperature.
Calculate junction temperature →A passively cooled finned heat sink made of black anodized aluminium (ε = 0.85) reaches 60 °C at an ambient temperature of 25 °C. Its envelope area is 0.10 m², the total fin surface 0.40 m². For natural convection, we assume α = 5 W/(m²·K).
T₁ = 60 + 273.15 = 333.15 K, T₂ = 25 + 273.15 = 298.15 K T₁⁴ − T₂⁴ = 1.2319 · 10¹⁰ K⁴ − 0.7902 · 10¹⁰ K⁴ = 4.417 · 10⁹ K⁴ q̇_rad = 0.85 · 5.670 · 10⁻⁸ W/(m²·K⁴) · 4.417 · 10⁹ K⁴ = 213 W/m² Q̇_rad = 213 W/m² · 0.10 m² = 21 W, α_rad = 213 W/m² / 35 K = 6.1 W/(m²·K) Q̇_conv = 5 W/(m²·K) · 0.40 m² · 35 K = 70 W → radiation share 21 W / 91 W ≈ 23 % With a fan (α = 50 W/(m²·K)): Q̇_conv = 700 W → radiation share ≈ 3 % Bare aluminium (ε = 0.09): Q̇_rad = 2.3 W instead of 21 W With natural convection, radiation contributes almost a quarter of the heat dissipation in this example, because α_rad at around 6 W/(m²·K) is of the same order of magnitude as α_conv. With a fan, its share drops to about 3 % and becomes negligible. Black anodizing increases the radiated power by a factor of about 9 compared with bare aluminium.
Whether you need to include radiation depends on the ratio of α_rad to α_conv. At surface temperatures up to about 100 °C and high emissivity, α_rad is around 5 to 8 W/(m²·K). That is a lot compared with natural convection and little compared with forced convection.
| Heat transfer mode | α_conv in W/(m²·K) | Relevance of radiation (ε ≈ 0.85) |
|---|---|---|
| Natural convection, air | 2 to 25 | High: α_rad ≈ 6 W/(m²·K) is of the same order of magnitude, always include radiation. |
| Forced convection, air | 25 to 250 | Low: at α = 50 W/(m²·K) and the same area about 10 %, less for finned heat sinks. |
| Forced convection, water and water-glycol | 100 to 20,000 | Negligible: almost all of the heat goes into the coolant. |
| Boiling and condensation | 2,500 to 100,000 | Negligible. |
Reference values for α according to Incropera et al., Fundamentals of Heat and Mass Transfer, and the VDI Heat Atlas. α_rad calculated for a surface temperature of 60 °C and 25 °C ambient.
Emissivity of metals and surfaces →The heat flux q̇ is a good first indicator for the cooling concept. What counts is the flux at the mounting surface of the cooler, where the heat passes from the component into the heat sink. The ranges are guideline values, not hard limits.
| Heat flux q̇ | Typical cooling concept | Suitable designs |
|---|---|---|
| below 0.3 W/cm² (below 3,000 W/m²) | Air cooling, passive or with fan | Extruded, impact-extruded and bonded fin heat sinks |
| 0.3 to 1 W/cm² (3,000 to 10,000 W/m²) | High-performance air cooling with fan or liquid cooling | Bonded fin heat sinks, pin fin heat sinks, cold plates with pressed-in tubes |
| above 1 W/cm² (above 10,000 W/m²) | Liquid cooling | Cold plates with pressed-in tubes, internally structured cold plates |
A thick base plate or a copper inlay spreads the heat and lowers q̇ at the cooler surface. That is why it pays to look at both areas: that of the component and that of the cooler.
Air cooling or liquid cooling? Decision guide →Not sure where your thermal path loses the most kelvin? COOLTEC supports you with calculation, simulation and production-ready implementation, free and without obligation.
Learn how to optimize cooling for high-tech applications – with solutions that are efficient, reliable, and ready to implement.