You calculate the Reynolds number as Re = v · Dₕ / ν from the mean flow velocity, the hydraulic diameter and the kinematic viscosity. In pipes and coolant channels, flow is laminar below about 2,300 and fully turbulent above about 10,000, with a transition range in between. The calculator determines Re directly from flow rate, channel geometry and coolant.
Whether the coolant flows laminar or turbulent in a channel decides how well it picks up heat from the channel wall and how much pressure the pump has to deliver. Which heat transfer correlation applies, and how strongly the pressure drop grows with flow rate, depends directly on the flow regime. That makes the Reynolds number one of the first figures to check when sizing a cold plate, before you calculate the heat transfer coefficient and pressure drop.
Channel cross-section
Enter the dimensions of a single channel. If the flow is split across several parallel channels, the calculator uses the share per channel. For other cross-sections, calculate Dₕ = 4 · A / P yourself and enter it as the inner diameter of a round pipe in "Enter velocity" mode.
The Reynolds number is a dimensionless quantity. It relates the inertial forces of the flow to the viscous forces of the fluid:
Re = ρ · v · Dₕ / η = v · Dₕ / ν
At low Reynolds numbers, viscous forces dominate: disturbances in the flow are damped and the fluid slides in parallel layers with a parabolic velocity profile. At high Reynolds numbers, inertial forces dominate: disturbances no longer die out, eddies mix the fluid across the flow direction and the velocity profile becomes flatter. Because Re is dimensionless, all quantities must be in consistent units. If you use Dₕ in mm, v belongs in mm/s and ν in mm²/s.
For flow in pipes and channels, based on the hydraulic diameter, these guide values apply:
Re < 2,300
Laminar
Layered flow, disturbances die out. Pressure drop rises linearly with v; in a round pipe the friction factor is f = 64 / Re. In developed flow the Nusselt number is constant: 3.66 in a round pipe at constant wall temperature and 4.36 at constant heat flux.
2,300 to approx. 10,000
Transition range
Laminar and turbulent phases alternate. Heat transfer and pressure drop scatter widely. The VDI Heat Atlas interpolates the Nusselt number here between the laminar and the turbulent value.
Re > 10,000
Fully turbulent
Strong cross-mixing and a thin near-wall boundary layer. The Nusselt number grows roughly with Re^0.8 (e.g. Dittus-Boelter), pressure drop roughly with v^1.75 to v².
The critical Reynolds number of about 2,300 marks the limit below which pipe flow reliably stays laminar: disturbances from the inlet or from wall roughness die out. Above it, the flow can become turbulent, but it does not have to. In very smooth pipes with a disturbance-free inlet, laminar flow has been observed well above 10,000.
For the upper limit there are two common conventions. Fluid mechanics textbooks often place the turbulent range from Re ≈ 4,000, because from there the friction factor follows the turbulent curve in the Moody chart. Classic heat transfer correlations such as Dittus-Boelter, on the other hand, only apply from Re ≈ 10,000, and Incropera and the VDI Heat Atlas also treat flow as fully turbulent only from there. For cold plate design, 10,000 is the more cautious value: between 4,000 and 10,000, pressure drop already behaves almost like turbulent flow, but heat transfer does not yet.
For non-circular cross-sections, the hydraulic diameter replaces the pipe diameter. It is four times the flow cross-section A divided by the wetted perimeter P:
Dₕ = 4 · A / P The mean velocity follows from the flow rate and the cross-section of one channel, v = V̇ / A. With V̇ in l/min and A in mm², the numerical equation is:
v [m/s] = V̇ [l/min] / (0.06 · A [mm²]) If a manifold splits the flow across n parallel channels, only the share per channel counts, i.e. V̇ / n. That is why the same coolant at the same total flow rate often flows laminar in a cold plate with many fine channels and turbulent in a single pressed-in tube.
For a given geometry and velocity, the kinematic viscosity ν sets the Reynolds number. The table shows typical values at ambient pressure (1.013 bar). A value of 1 · 10⁻⁶ m²/s equals 1 mm²/s.
| Fluid | Temperature | Density ρ [kg/m³] | Dyn. viscosity η [mPa·s] | Kin. viscosity ν [10⁻⁶ m²/s] |
|---|---|---|---|---|
| Water | 20 °C | 998 | 1.00 | 1.00 |
| Water | 40 °C | 992 | 0.65 | 0.66 |
| Water | 60 °C | 983 | 0.47 | 0.47 |
| Water/ethylene glycol 70/30 vol% | 20 °C | ≈ 1,040 | ≈ 2.3 | ≈ 2.2 |
| Water/ethylene glycol 50/50 vol% | 20 °C | ≈ 1,070 | ≈ 4.1 | ≈ 3.8 |
| Air | 20 °C | 1.20 | 0.018 | 15.1 |
Glycol values depend on concentration and product. A 50/50 mixture is about 3.5 · 10⁻⁶ m²/s by mass percent and about 3.8 · 10⁻⁶ m²/s by volume percent. Ready-mixed coolants can deviate slightly because of inhibitors, and propylene glycol mixtures are considerably more viscous at the same concentration. For the design, use the data sheet of your coolant.
Sources: water and air from the VDI Heat Atlas (VDI-Wärmeatlas) and Incropera et al., Fundamentals of Heat and Mass Transfer. Ethylene glycol mixtures calculated from the viscosity and density correlations in the MEGlobal Ethylene Glycol Product Guide, rounded.
The viscosity of water drops sharply with temperature. From 20 °C to 60 °C, ν falls from 1.00 to 0.47 · 10⁻⁶ m²/s, roughly a factor of 2. At the same velocity, the Reynolds number therefore doubles. A channel that runs laminar in the lab with 20 °C water can be in the transition range in operation at a coolant temperature of 50 to 60 °C. Use the mean coolant temperature in the channel, and also check the coldest operating case.
Glycol works the other way. A 50/50 mixture at 20 °C is almost four times as viscous as water, so at the same velocity the Reynolds number drops to just over a quarter. Re = 8,000 with water becomes about Re = 2,100, which is laminar. Glycol mixtures also have lower thermal conductivity and heat capacity than water. At low temperatures, for example during a cold start below 0 °C, their viscosity rises sharply again.
Turbulent flow improves heat transfer because eddies carry cooler fluid from the channel core to the wall. In the fully turbulent range, the heat transfer coefficient α grows roughly with v^0.8: doubling the velocity gives about 75 % more α. In the same step, however, pressure drop rises to about 3.4 to 4 times, because it grows roughly with v^1.75 to v². Beyond a certain point, every further increase mainly costs pump power.
Laminar flow can still cool very well. In fully developed laminar flow, the Nusselt number Nu = α · Dₕ / λ is constant, so α ∝ 1 / Dₕ: the smaller the channel, the higher the heat transfer. A round channel with Dₕ = 0.5 mm reaches α ≈ 5,500 W/(m²·K) with water at 40 °C (thermal conductivity λ ≈ 0.63 W/(m·K), Nu = 4.36), even though Re is only a few hundred. A 10 mm tube in turbulent flow at 1.5 m/s (Re ≈ 23,000) achieves about 8,000 W/(m²·K). Micro-channels also offer much more wetted area per footprint.
In real cold plates, the flow is rarely fully developed. Short channels, bends, pins and fins keep disrupting the boundary layer, so heat transfer is above the value for developed flow. The Reynolds number tells you which range you are in and which correlation fits. For the actual design, you then need the heat transfer coefficient and the pressure drop curve.
Water at 40 °C (ν = 0.658 · 10⁻⁶ m²/s) flows through a cold plate at 8 l/min. A manifold splits the flow evenly across eight parallel rectangular channels with a 10 mm × 3 mm cross-section.
V̇ per channel = 8 l/min / 8 = 1 l/min = 1.667 · 10⁻⁵ m³/s A = 10 mm · 3 mm = 30 mm² = 3.0 · 10⁻⁵ m² v = V̇ / A = 1.667 · 10⁻⁵ / (3.0 · 10⁻⁵) ≈ 0.556 m/s Dₕ = 2 · 10 · 3 / (10 + 3) ≈ 4.62 mm Re = v · Dₕ / ν = 0.556 · 0.00462 / (0.658 · 10⁻⁶) ≈ 3,900 2,300 < Re < 10,000 → transition range At 1 l/min per channel, the flow is in the transition range. With 20 °C water (ν = 1.00 · 10⁻⁶ m²/s), Re drops to about 2,560, just above the laminar limit. If the full 8 l/min flowed through a single channel of the same size, v would rise to 4.4 m/s and Re to about 31,000: fully turbulent, but with many times the pressure drop.
Laminar, turbulent or in between? COOLTEC designs channel geometry, flow rate and cold plate for your heat load, free and without obligation.